Product specification
Interlock locking systems
System 2
The locking system from Zystm is developed specifically for
hospitals and laboratories. Interlock is primarily used when
there is a requirement for pass through cabinets linking
two rooms with separate access door fronts which do not
open simultaneously preventing cross contamination.
The interlock system function ensures ease of cleaning
and maintenance to the pass through cabinet for optimal
hygiene.
Interlock system 2
This system is primarily used when both connecting rooms
have differential pressure or there is a requirement to
delay the opening of the cabinets after they have been
unlocked. The interlock locks can be used on ordinary cabinet fronts or fire rated and isotope protected cabinets. An
electromagnet combined to a control unit is used to lock
the cabinet. The control unit must be placed outside the
cabinet and wired up to the lock. The control unit must be
supplied with 230V 10A electrical supply.
Interlock system 2 is supplied with contactless buttons
which must be activated to open one of the door fronts.
There must also be sufficient space adjacent to the cabinet
for siting the contactless buttons.
The time delay of opening can be adjusted on the control unit.
Use of interlock system 2
When both fronts are closed on
the cabinet the interlock system
is locked and the fronts are
retained so that the differential
pressure difference will not force
the fronts open. The light in the
indicator on the contactless
button shines green indicating
the front can be opened.
When you wish to open the
otherside of the cabinet the lock
is activated by placing your hand
over the contactless button.
The light indicator will now
change to red indicating the
opposite front can’t be opened.
If the timer function is choosen
(delayed opening), the indicator
will start to flash red when both
the door fronts are closed and
will continue flashing until the
adjusted delay has expired.
During this time it will be
possible to open both door fronts
at the same time. When the
delay has expired both indicators
shine green only allowing one of
the door fronts to open at a
time.